5 SETTINGS
b) BASIC CONFIGURATION

PATH: SETTINGS
SYSTEM SETUP
 PMU 1 BASIC
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
N60 Network Stability and Synchrophasor Measurement System

PHASOR MEASUREMENT
PMU 1
FUNCTION: Disabled
PMU 1 IDCODE:
1
PMU 1 STN:
GE-UR-PMU
PMU 1 SIGNAL SOURCE:
SRC 1
PMU 1 CLASS:
M-CLASS
PMU 1 FORMAT:
Integer
PMU 1 STYLE:
Polar
PMU 1 RATE:
10/sec
PMU 1 PHS-1:
Off
PMU 1 PHS-1
NAME: GE-UR-PMU-PHS-1
PMU 1 PHS-14:
Off
PMU 1 PHS-14:
NAME: GE-UR-PMU-PHS-14
PMU 1 A-CH-1:
Off
PMU 1 A-CH-1:
NAME: AnalogChannel1
PMU 1 A-CH-16 (16):
Off
PMU 1 A-CH-16 (16):
NAME: AnalogChannel16
PMU 1 D-CH-1:
Off
PMU 1 D-CH-1
NAME: DigChannel1
PMU 1 D-CH-1
NORMAL STATE: Off
BASIC CONFIGURATION
PMU1(6)
Range: Enabled, Disabled
Range: 1 to 65534 in steps of 1
Range: 32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
Range: Available signal sources
Range: None, CLASS M, CLASS P
Range: Integer, Floating-point
Range: Polar, Rectangular
Range:1/sec, 2/sec, 4/sec, 5/sec, 10/sec, 12/sec, 15/sec,
20/sec, 25/sec, 30/sec, 50/sec, 60/sec, 100/sec, 120/sec
Range: Available synchrophasor values
Range: 16 -character ASCII string
Range: Available synchrophasor values
Range: 16 -character ASCII string
Range: Available FlexAnalog values
Range: 16 -character ASCII string
Range: Available FlexAnalog values
Range: 16 -character ASCII string
Range: Available FlexLogic operands
Range: 16 character ASCII string
Range: Off, On
5.4 SYSTEM SETUP