Versamax General Product Specifications - GE VersaMax IC200PWR001 User Manual

Table of Contents

Advertisement

VersaMax General Product Specifications

VersaMax products should be installed and used in conformance with product-
specific guidelines, as well as the specifications listed in the following table.
Environmental
Vibration
Shock
Operating Temperature
Storage Temperature
Humidity
Enclosure Protection
EMC Emission
Radiated, Conducted
EMC Immunity
Electrostatic Discharge
RF Susceptibility
Fast Transient Burst
Surge Withstand
Conducted RF
Isolation
Dielectric Withstand
Power Supply
Input Dips, Variations
GFK-1504N
IEC68-2-6
IEC68-2-27
IEC529
CISPR 11/EN 55011
CISPR 22/EN 55022
FCC 47 CFR 15
EN 61000-4-2
EN 61000-4-3
ENV 50140/ENV 50204
EN 61000-4-4
ANSI/IEEE C37.90a
IEC255-4
EN 61000-4-5
EN 61000-4-6
UL508, UL840, IEC664
EN 61000-4-11
Chapter 1 Introduction
1G at 57-150Hz, 0.012in p--p at 10-57Hz
15G, 11ms
0 to +60 deg C ambient
-40 to +60 deg C ambient for I/O carriers,
communications carrier, interposing I/O terminals, and
auxiliary I/O terminals
-40 to +85 deg C
5% to 95%, noncondensing
Steel cabinet per IP54:
protection from dust & splashing water
Industrial Scientific & Medical Equipment
(Group 1, Class A)
Information Technology Equipment (Class A)
Referred to as FCC part 15,
Radio Devices (Class A)
8KV Air, 4KV Contact
10V
/m, 80 to 1000Mhz, 80% AM
rms
10V
/m, 900MHz ±5MHZ
rms
100%AM with 200Hz square wave
2KV: power supplies, 1KV: I/O, communication
Damped Oscillatory Wave: 2.5KV:
power supplies, I/O [12V-240V]
Damped Oscillatory Wave: Class II,
power supplies, I/O [12V-240V]
2 kV cm(P/S); 1 kV cm (I/O and communication
modules)
10V
, 0.15 to 80Mhz, 80%AM
rms
1.5KV for modules rated from 51V to 250V
During Operation: Dips to 30% and 100%,
Variation for AC ±10%,
Variation for DC ±20%
1
1-19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents