Chapter 1. Introduction
Specifications
1.1
1.1.1
Part Numbers
ICRXICTL000
ICRXIACCIDM01
ICRXIACCBPL
(rev B or later required)
IC690ACC001
ICRXIACCEPK01A
ICRXIACCCPK01A
ICRXIACCCBL01A
1.1.2
Mechanical Specifications
Dimensions (L×W×D):
Weight:
1.1.3
RXi Controller Environmental Specifications
Vibration
Shock
Ambient Operating Temperature
Storage Temperature
Humidity
Environment
Altitude
A Pollution Degree 2 environment:
2
RXi Controller with lid
Backplate
RXi Controller with lid
Backplate
Note:
The RXi Controller shall be installed in a location that is not exposed to
corrosive gases or liquids, rain, or direct sunlight, and that meets the
environmental specifications listed below.
Description
Pollution Degree 2 applies where there is only non-conductive pollution that might
temporarily become conductive due to occasional condensation.
PACSystems* RXi Distributed IO Controller User Manual
RXi Controller
Intelligent Display Module (IDM)
Optional Backplate for DIN rail mounting
Real Time Clock (RTC) battery, replacement
Energy Pack. Includes base, CapPack module and Energy Pack to
Controller cable.
Replacement CapPack module
Replacement 0.3m (12") Energy Pack to Controller cable
191.8 mm × 115.6 mm × 78.7 mm
(7.55" × 4.55" × 3.1")
223.5 mm ×115.6 mm × 17.8 mm
(8.80" × 4.55" × 0.7")
1.814 Kg (4 lbs.)
0.908 Kg (2 lbs.)
10 - 57 Hz, 0.006 in. displacement peak-peak
57 - 500 Hz, 1.0 g acceleration
15G, 11ms
Version ICRXICTL000-EH and later:
Panel mount (metal panel): -25C to +55C: [inlet] (-13°F to 131°F)
DIN rail mount: -25C to +50C: [inlet] (-13°F to 122°F)
Version ICRXICTL000-DH and earlier:
Panel mount (metal panel): -25C to +50C: [inlet] (-13°F to 122°F)
DIN rail mount: -25C to +45C: [inlet] (-13°F to 113°F)
-40C to +85C (-40°F to 185°F)
5% to 95%, non-condensing
Pollution Degree 2 as defined below.
0–2000 m
Comments
GFK-2816F