Switch # 2 - Not Used; Switch # 3 - Main/ D.set: Generator Parameters; Switches # 5, 6 - Language Selection; Switch # 7 - Expanded Settings - GE ASTAT XT QT 0008U Series User Manual

Solid state soft starter
Table of Contents

Advertisement

Switch # 2 – Not used
5.5.2
Switch # 3 – Main/ D.Set: Generator Parameters
5.5.3
Refer to section 8.17 page 71 for information regarding the operation of this switch.
WARNING
When operating in D.Set: Generator Parameters, the motor must be
loaded to avoid vibration during starting and stopping.
Switches # 5, 6 – Language Selection
5.5.4
Language selection defined by the switch settings.
Language
English
Italian
German
Spanish
Switch # 7 – Expanded Settings
5.5.5
EXPANDED SETTINGS corresponds to:
Parameter
Starting Voltage
Ramp UP Time
Ramp DOWN Time
Phase Loss
Max Slow SP Time
OC or Wrong CON.
protection in Inside Delta
configuration.
Notes:
(1)
Setting the Starting Voltage to lower than 10% is not practical for loaded motors.
(2)
Refer to section 7 page 59. See Phase Loss protection and refer to the warning below.
(3)
Refer to section 7 page 59. See OC or Wrong CON. protection.
WARNING
EXPANDED SETTINGS are for use in very special applications only!
Operator's
Do not set to switch #7 to ON unless ASTAT-XT is significantly larger than the
responsibility!
motor! When using expanded settings for the ASTAT-XT you must be extremely
careful to avoid damaging the motor or ASTAT-XT.
Only cancel Phase Loss protection when the operator is sure that no real phase
loss exists and Phase Loss protection is activated.
This situation can occur in rare cases when there is no real fault but the ASTAT-XT
recognizes unusual behaviour like when THDV (Total Harmonic Distortion in
Voltage) in the network is high.
If this is a true case of Phase Loss then after cancelling Phase Loss protection the
motor will single phase and most likely be tripped by the over load protection
mechanism.
Switch # 8 – Software Lock
5.5.6
The software lock prevents undesired parameter modifications.
When locked, pressing the Set, ▼or ▲ keys causes the LCD to display Access Locked.
• Installation
50
Switch #5
Switch #6
Off
Off
Off
On
On
Off
On
On
Range Switch #7 - Off
10-50%
1-30 seconds
1-30 seconds
Enabled
(2)
1-30 seconds
Protection active in normal
set
(3)
Position of Switches
Range switch #7 - On
5
-80%
(1)
1-90 seconds
1-90 seconds
Enabled/Disabled
(2)
1-60 seconds
Protection active in high set
(3)