Terminal 53 And 54 Switches; Serial Communication - GE AF-600 FP Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Installation

2.5.8.6 Terminal 53 and 54 Switches

Analog input terminals 53 and 54 can select
either voltage (0–10 V) or current (0/4–20 mA)
2
2
input signals
Remove power to the adjustable frequency drive
before changing switch positions.
Set switches A53 and A54 to select the signal
type. U selects voltage, I selects current.
The switches are accessible when the keypad has
been removed (see Figure 2.36). Note that some
option cards available for the unit may cover
these switches and must be removed to change
switch settings. Always remove power to the unit
before removing option cards.
Terminal 53 default is for a speed reference signal
in open-loop set in DR-61 Terminal 53 Switch
Setting
Terminal 54 default is for a feedback signal in
closed-loop set in DR-63 Terminal 54 Switch
Setting
Figure 2.36 Location of Terminals 53 and 54 Switches
2-16
AF-600 FP Design and Installation Guide

2.5.9 Serial Communication

RS-485 is a two-wire bus interface compatible with multi-
drop network topology, i.e., nodes can be connected as a
bus, or via drop cables from a common trunk line. A total
of 32 nodes can be connected to one network segment.
Repeaters divide network segments. Note that each
repeater functions as a node within the segment in which
it is installed. Each node connected within a given network
must have a unique node address across all segments.
Terminate each segment at both ends using either the
termination switch (S801) of the adjustable frequency
drives or a biased termination resistor network. Always use
shielded twisted pair (STP) cable for bus cabling, and
always follow good common installation practice.
Low-impedance ground connection of the shield at every
node is important, including at high frequencies. Thus,
connect a large surface of the shield to ground, for
example with a cable clamp or a conductive cable
connector. It may be necessary to apply potential-
equalizing cables to maintain the same ground potential
throughout the network. particularly in installations with
long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the adjustable frequency drive,
always use shielded motor cable.
Cable
Impedance
Cable length
Table 2.8
130BT310.10
DET-768A
Shielded twisted pair (STP)
120 Ω
Max. 4,000 ft [1,200 m] (including drop lines)
Max. 1,650 ft [500 m] station-to-station

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents