Modbus User Map; Real-Time Clock - GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

PRODUCT SETUP
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-12: Commands mapping table
Description
Off
Virtual Input 1
Virtual Input 2
...
Virtual Input 64

5.3.5 Modbus user map

SETTINGS  PRODUCT SETUP  MODBUS USER MAP
 MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the
line (converted from hex to decimal format). The corresponding value (if programmed) displays in the
ADDRESS
line. A value of "0" in subsequent register
5
incremented by 1. An address value of "0" in the initial register means "none" and values of "0" display for all registers.
Different
ADDRESS
The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser;
enter the IP address of the B30 in a web browser and click the option.

5.3.6 Real-time clock

5.3.6.1 Menu
SETTINGS  PRODUCT SETUP  REAL TIME CLOCK
 REAL TIME
 CLOCK
The relay contains a real time clock (RTC) to create time stamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchronizing
5-94
Value
0
1
2
...
64
ADDRESS 1:
VALUE:
ADDRESS 256:
VALUE:
ADDRESS
values can be entered as required in any of the register positions.
SYNCRONIZING SOURCE:
None
REAL TIME CLOCK
EVENTS: Disabled
IRIG-B SIGNAL TYPE:
None
 PRECISION TIME
 PROTOCOL (1588)
 SNTP PROTOCOL
 LOCAL TIME
0
Range: 0 to 65535 in steps of 1
0
0
Range: 0 to 65535 in steps of 1
0
lines automatically returns values for the previous
Range: None, PP/IRIG-B/PTP/Other, IRIG-B/PP/PTP/
Other, PP/PTP/IRIG-B/Other
Range: Enabled, Disabled
Range: None, DC Shift, Amplitude Modulated
See below
See below
See below
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
VALUE
lines
ADDRESS