Modbus User Map; Real Time Clock - GE C30 Instruction Manual

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS
EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any
data from the C30 memory map can be configured to be included in an EGD exchange. The settings are the starting
Modbus register address for the data item in decimal format. Refer to Appendix B for the complete Modbus memory
map. Note that the Modbus memory map displays shows addresses in hexadecimal format. as such, it will be neces-
sary to convert these values to decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values),
only the first Modbus address is required. The EGD exchange configured with these settings contains the data items
up to the first setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid
Modbus addresses and the fourth is 0, the produced EGD exchange will contain three data items.
PATH: SETTINGS
PRODUCT SETUP
 MODBUS USER MAP
MESSAGE
MESSAGE
MESSAGE
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
line (converted from hex to decimal format). The corresponding value displays in the
ADDRESS
value of "0" in subsequent register
by "1". An address value of "0" in the initial register means "none" and values of "0" display for all registers. Different
values can be entered as required in any of the register positions.
ADDRESS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 REAL TIME
 CLOCK
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


MODBUS USER MAP

ADDRESS
1:
VALUE:
0
ADDRESS
2:
VALUE:
0
ADDRESS
3:
VALUE:
0
ADDRESS 256:
VALUE:
0
lines automatically returns values for the previous
ADDRESS


REAL TIME CLOCK

SYNCRONIZING SOURCE:
None
REAL TIME CLOCK
EVENTS: Disabled
IRIG-B SIGNAL TYPE:
None
 PRECISION TIME
 PROTOCOL (1588)
 SNTP PROTOCOL
 LOCAL TIME
C30 Controller System
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
Range: Enabled, Disabled
Range: None, DC Shift, Amplitude Modulated
See below
See below
See below
5.2 PRODUCT SETUP
5.2.5 MODBUS USER MAP
line. A
VALUE
lines incremented
ADDRESS
5.2.6 REAL TIME CLOCK
5-55
5

Advertisement

Table of Contents
loading

Table of Contents