Master Programming Level

Timers

SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
PAS (Positive Alarm Sequence) Delay
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five sec-
onds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices pro-
grammed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine sec-
onds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be programmed for either PAS or Pre-signal
operation. Refer to"Edit Detector" on page 51 for programming details.
Waterflow Delay
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-five
seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
AC Loss Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
Timer Screen #2
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central station.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing
System Setup Screen #2. The following screen will be displayed:
TIMERS
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLOW
Timer Screen #1
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all
devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear:
RANGE 0-180 SECONDS
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays of
the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a Waterflow
delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing Timer Screen
#1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
The reporting of a loss of AC power to a central station can be delayed by programming the length of the
desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2 to display the fol-
lowing:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
TIMERS
000
1=AC LOSS DELAY
000
2=CTRL MOD DLY
000
Timer Screen #2
PAS DELAY
PAS Delay Screen
Programming
02
000
71