Voice Options

2.
Panel ID
NOTE: Only the SIA format sends the panel ID when reporting.
Receiver Configuration
The 6820 network can report events to as many as 68 receivers. See Appendix B for panel/receiver relationship numbers. Each receiver can
be a phone number and reporting format. Phone numbers can be up to forty digits long.
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options Menu.
4.
Select 3 for Receiver Configuration.
5.
Select Panel to Program and press ENTER.
6.
Enter the receiver number that you want to report to. The receiver numbers available will correspond with what panel number you
entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See Appendix B
for receiver number.
Available Format choices are:
Contact ID
SIA500
SIA8
SIA20
Ethernet
Cellular
UNUSED
Communicator Reporting Table
The Communicator Report Table specifies event reporting for each panel on the network. Each row in the table specifies a panel, event types
to report, primary and backup receiver numbers, and report by point or zone. Associated with the receivers are account number and daily test
option. The table can have up to 99 rows.
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
4.
Select 4 for Communicator Reporting Table.
5.
Press * to add rows, Press ENTER to edit data
panel number
primary receiver number
secondary receiver number
6.3 Voice Options
6.3.1 Edit Timers
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 1 for Edit Timers
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Panel: 03 YYYY
R009:321456 N
R013:987456 N
<Help Text>
P#ASTP Prit Sect
01=03YYYY 009N 013N
02=02NNYN 015N 014Y
* = Add Row
panel number
report alarms
report supervisories
Figure 6.1 Communicator Reporting
test primary account
test secondary account
report event by point (Y=point, N=zone)
report troubles
Network Management
69

Advertisement