Honeywell Fire-Lite Alarms ES-1000X Manual page 59

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Not Used ****
Not Used *
Smoke Conventional
User-Defined-5
Heat Conventional
User-Defined-6
1
Medic Alert
User-Defined-7
1
Hazard Alert
User-Defined-8
1
Tornado Alert
User-Defined-9
Phone
User-Defined-10
Tamper
User-Defined-11
Supervisory
User-Defined-12
2
Supervisory AR
User-Defined-13
3
HVAC Ovrride
Power Monitor
User-Defined-14
Trouble Monitor
User-Defined-15
Process Monitor
User-Defined-16
Process Monitor AR
User-Defined-17
MNS Event
Not Used ***
Ack Switch
Sil Switch
Reset Switch
Drill Switch
PAS Bypass
3
HVAC Restart
2
Drill Switch AR
Wireless Gateway
1
Combination systems employing these non-fire monitor types require the SLC loop to be programmed by the installer for Class B
operation and isolator modules must be employed on each non-fire branch of the SLC as per Figure 13 in the SLC Wiring Manual
(document number LS10201-000FL-E). Fire and non-fire devices must not be used on the same SLC branch. For UL2017 compliance,
The ANN-LED annunciator must be used to indicate the active, dedicated zone or device
2
For entries ending in AR, AR refers to AutoResettable.
3
For HVAC Restart and HVAC Ovrride descriptions, refer to "Monitor Module Operation" on page 144.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Fire Alarm
same as previous (Pull-Station)
Fire Alarm Delayed
same as previous (Waterflow)
Fire Alarm
same as previous (Monitor)
not used
not used
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
General Purpose Signaling, latching
same as previous (Medic-Alert)
General Purpose Signaling, latching
same as previous (Hazard-Alert)
General Purpose Signaling, latching
same as previous (Tornado-Alert)
future use
same as previous (Phone)
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
same as previous (Supervisory)
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
Switch Supervisory, nonlatching (tracking)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
General Purpose Signaling, latching
1
same as previous (Process-Monitor)
1,2
General Purpose Signaling, nonlatching (tracking)
same as previous (Process-Monitor-AR)
Allows the Mass Notification System to override FACP programming and turn off designated active outputs
not used
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
Switch (see note 2)
Acts like panel Drill Key, nonlatching (tracking)
SWIFT gateway needs this type to display wireless troubles at the FACP
Action When Activated
Table 3.1 Monitor Types