Programming
SYSTEM SETUP

1=TIMERS

2=NAC
3=RELAYS
System Setup Screen #2
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
84
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens
which allow the programmer to select the week of the month that daylight savings
time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will
select the second week and 3 will select the third week, while in the second sub-
screen, pressing 1 will select the fourth week and 2 will select the last week of the
selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen
which allows the programmer to select the month that daylight savings time will
end. In this sub-screen, pressing 1 will select September, 2 will select October and
3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens
which allow the programmer to select the week of the month that daylight savings
time will end. In the first sub-screen, pressing 1 will select the first week, 2 will
select the second week and 3 will select the third week, while in the second sub-
screen, pressing 4 will select the fourth week and 5 will select the last week of the
selected month.
3.6.5.4 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by
pressing 1 while viewing System Setup Screen #2. The following screen will be
displayed:
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLOW
1=AC LOSS DELAY

3.6.5.4.1 PAS (Positive Alarm Sequence) Delay

The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001
to 180 seconds for all devices programmed for PAS, press 1 while viewing Timer
Screen #1. The following display will appear:
RANGE 0-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay
time consisting of three digits, such as 005 for five seconds. Upon entering the third
digit, the time delay will be stored in the control panel memory and the display will
return to the Delay Screen which will indicate the new delay time.