Appendix I: Open/Short/Ground Trip Values - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Table I.1 lists the earth fault resistance detection for each applicable terminal on the FACP.
Table I.2 lists the open/short trip values and restoral values for the NAC circuits on the FACP.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023

Appendix I: Open/Short/Ground Trip Values

Output Circuit
Remote Sync
Remote Sync
NAC 1-4
NAC 1-4
ANN Bus
ANN Bus
Aux Power
Aux Power
SLC
SLC
Table I.1 Earth Fault Trip Values
Circuit
NAC 1-4
Shorts below 1.4K
NAC 1-4
Opens above 35K
Remote Sync
Shorts below 1.5K
Remote Sync
Opens above 45K
Table I.2 NAC Open/Short Trip Values
Terminal
Trip Resistance (in ohms)
+
-
+
-
A
B
+
-
+
-
Trip Resistance (in ohms)
203K
176K
203K
176K
138K
143K
174K
175K
52K
117K
Restore Value
2.2K
21K
2.3K
26K
157