Read Status
Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a
detector with address 001 on the SLC loop is entered, a display similar to the following will appear:
The information in the preceding display includes:
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector)
NORTH CLASSROOM - the Adjective/Noun label for this device
Z005 - the first of five possible assigned software zones
1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
V - Alarm Verification Enabled (V = Yes, * = No)
S - Silenceable for control modules (S = Yes, * = No)
W - Walktestable for control and monitor modules (W = Yes, * = No)
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming information
about the selected device, such as:
Enable/Disable Status
Device Type
Alarm Verification On/Off (for detectors)
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
Pre-Signal Yes/No (for detectors and monitor modules)
Zone Assignments (five maximum)
Chamber Value
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
MNS Override Enabled/Disabled (for control modules)
Wireless Yes/No (for detectors only)
Sounder Base Yes/No (for detectors only)
Sounder Base Values and Zone Assignments (for detectors only)
4.23.2 Zones
READ STATUS
1=SYSTEM POINT

2=ZONES

Read Status Screen #1
From the preceding screens, the control panel operator can view:
Zones Installed - all software zones programmed into the system (255 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 253 reserved for PAS, 254 reserved for Pre-signal, 255 reserved for
Two Stage, and 252 for Local Alarm
Zone Type - the Type assigned to each installed zone (default is Alarm)
Zone Message - the Message assigned to each installed zone
4.23.3 Trouble Reminder
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2
The screen indicates whether the Trouble Reminder feature is set to sound every 4 or 24 hours.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed.
ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1
Pressing 1 while viewing Read Status Screen #2 will display the following screen:
TROUBLE REMINDER
TROUBLE REM
Z005
V
1D001
1=SPECIAL PURPOSE
2=ZONE TYPE
3=ZONE MESSAGE
Zones Screen #2
24HR
Operating Instructions
ZONES
111