Optional Module Installation
no connection

ANN-LED Annunciator Module

Specifications
Max. ANN-BUS Voltage: 24 VDC
Max. Current:
Alarm: 68 mA
Standby: 28 mA
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Must be installed adjacent to the main FACP operator interface to meet UL 2017 standards
For indoor use in a dry location only
For Canadian applications, the ANN-LED must be installed in a secure/protected room
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
P1
Pin #
1
LED1
2
LED2
3
LED3
4
LED4
5
LED5
6
LED6
7
LED7
8
LED8
9
LED9
10
LED10
11
LED Power
12
P2
Pin #
1
LED11
2
LED12
3
LED13
4
LED14
5
LED15
6
LED16
7
LED17
8
LED18
9
LED19
10
LED20
11
LED Power
12
no connection
Figure 2.23 ANN-LEDs (shown in possible stacked configuration)
Figure 2.22 ANN-I/O LED Wiring
Installation
Cathode
LEDs
Anode
Cathode
LEDs
Anode
39