Optional Module Installation

2.8 Optional Module Installation
WARNING: RISK OF ELECTRIC SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR
WIRING.
2.8.1 SLC-3LS Loop Expander Module Installation
The SLC-3LS Card provides an additional SLC loop to the FACP. A maximum of 2 cards is allowed in the system, offering a total of 3 SLC
loops. If an IPOTS-COM is also used in the system, it should be installed after installing any SLC-3LS cards. Refer to the SLC-3LS Installa-
tion Document #LS10195-000FL-E for installation and wiring instructions.
2.8.2 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A
jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows
disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a
Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal
box. Note that a Disconnect LED will illuminate after the module is installed in the ES-1000X. In addition, the System Trouble LED will
turn on to indicate the Disconnect condition.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Note: The 4XTMF Module is not directly suitable for transmitting a reverse polarity supervisory signal. For
applications using reverse polarity of a supervisory signal, refer to the Keltron Wiring Document #52776.
+
-
+
-
1
2
3 4
5 6
TBL Jumper
Figure 2.14 4XTMF Transmitter Module
}
Remote Alarm (power-limited)*
}
Remote Trouble (power-limited)*
No connection
}
Municipal Box (non-power-limited)*
+
-
7
Polarities are shown for module activation
Connect to FACP J12 & J13
Installation
* Wiring from these
terminals can exit the
protected premises.
Dummy load
terminals 6 and 7
(4.7kΩ, ¼ watt
resistor) if Municipal
Box is not connected.
Disconnect LED
Disconnect Switch
shown in
disconnect position
29