Wire Requirements
D.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
NAC Load
(Amps)
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
Notes:
1.
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2011 Edition) Table
8, Conductor Properties.
2.
These distances reflect the worst case scenario and are based on the current draw of the highest candela strobes at the low end of the
supported NAC voltage with the entire load at the end of the circuit. Further distances can be achieved by performing a point-to-point
voltage calculation that more accurately reflects the specific devices used and how they are dispersed on the circuit.
3.
If using Gentex brand notification appliances, the "UL Max" current rating published in their data sheets, must be used in order to
maintain performance under low battery conditions with the maximum wire resistances shown in the table above.
142
Max.
Max. allowable wire pair length
allowable
total loop
resistance
AWG 12
AWG 14
(ohms)
solid
solid
12
3780
6
1890
4
1260
3
945
2.4
760
2
630
1.71
540
1.5
475
1.33
420
1.2
380
1.09
345
1
320
Table D.2 NAC Wiring Requirements for FACP
CLASS-B
(feet)
AWG 16
AWG 18
solid
solid
2380
1495
940
1200
750
470
800
500
314
595
375
235
478
300
188
400
250
158
340
234
134
298
187
118
264
166
105
240
150
94
216
136
86
200
125
79
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
CLASS-A
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
1890
1190
945
600
630
400
473
298
380
239
315
200
270
170
238
149
210
132
190
120
173
108
160
100
NAC Wiring
AWG 18
solid
748
470
375
235
250
157
188
118
150
94
125
79
107
67
94
59
83
53
75
47
68
43
63
40