Programming
The Phone Number screen is used to enter the Central Station phone number that the Communicator will be contacting. A maximum of 20
characters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = 2 seconds pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor to
the right one position. Enter the second digit and repeat the process until all digits are entered. Press the Enter key to store the phone number
in memory.
Communication Format
POTS XXX COMM PATH
1=COMM FORMAT
ADEMCO CONTACT ID
POTS Comm Path Screen #3
The Communication Format is determined by the type of receiver that the Communicator is transmitting to. Consult your Central Station for
proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event
codes.
Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen. The following table
describes each format:
Test Time Interval
The test report sent to the Central Station phone number may be sent once every 1, 2, 3, 4, 6, 8, 12, or 24 hours. Pressing 1 while viewing
POTS (XXX) Comm Path #4 will toggle the available settings. Refer to the table on page 43 for permissible settings.
24 Hour Test Time
POTS XXX COMM PATH
1=TEST TIME INT
2=24HR TEST TIME 0100
POTS Comm Path Screen #4
Use the 24 Hour Test Time screen to program the time that the Communicator will transmit the 24 Hour Test to the Central Station. A flash-
ing cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time (0000 =
midnight and 2359 = 11:59PM). Setting the 24 Hour Test Time on either path sets the time for both paths. However, the secondary path will
send out a test 15 minutes after the primary path.
Ethernet
XXX COMM PATH
1=POTS
2=ETHERNET
Comm Path Screen #1
Enable
To enable the Ethernet connection, press 1 while viewing the Ethernet Options Screen #1 to change the display to Enabled Yes. Each press of
the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Central Station Account
ETHERNET OPTIONS
1=ENABLED
2=CS ACCOUNT
Ethernet Options Screen #1
Enter the City ID, Central Station ID, and Account Code all provided by the monitoring station.
82
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed:
Screen Selection
ADEMCO CONTACT ID
SIA 8
SIA 20
Table 3.2 Communication Formats
Pressing 2 while viewing POTS (XXX) Comm Path #4 will cause the following screen to be displayed:
24
To configure the communication method to contact central station as an ethernet connection, select 2 for Ether-
net. The following screens will display.
ETHERNET OPTIONS
1=ENABLED
2=CS ACCOUNT
Ethernet Options Screen #1
Press 2 on Ethernet Options Screen #1 to display the following:
NO
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA 8
3=SIA 20
Communication Format Description
Contact ID, DTMF, 1400/2300 ACK
Security Industry Association, 8 messages per call
Security Industry Association, 20 messages per call
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
ETHERNET OPTIONS
NO
1=SUPV. SETTINGS
NFPA 2013 DUAL PATH
Ethernet Options Screen #2
CS ACCOUNT
1=CITY ID
0000
2=CS ID
0000
3=ACC CODE
000000
24 Hour Test Time Screen
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level