ES-200X
Whitney Even on 06/22/2022
Intelligent Addressable FACP
with Communicator
General
The ES-200X is the latest intelligent addressable Fire Alarm Control
Panel (FACP) from Fire•Lite Alarms. The ES-200X comes with a
pre-installed communicator and supports up to 198 addressable
devices (99 detectors and 99 modules). With an extensive list of
powerful features, the ES-200X programs just like Fire•Lite's other
addressable products, yet fits into applications previously served
only by conventional panels.
The pre-installed IPOTS-COM is a dual technology (POTS and IP)
communicator. The POTS transmits system status (alarms, troubles,
AC loss, etc.) to a Central Station via the public switched telephone
network. The IP communicator's internet monitoring capability sends
alarm signals over the Internet saving the monthly cost of two dedi-
cated business telephone lines. Although not required, the second-
ary telephone line may be retained providing backup communication
over the public switched telephone line. Optional cellular reporting is
available using the CELL-MOD or CELL-CAB-FL.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can
be uploaded/downloaded via the panel's USB port (and USB cable)
or via an ethernet connection using the IPOTS-COM communicator.
The USB port also allows for the download or upload of the entire
program, history file, walk-test data, current status and system volt-
ages by means of a USB flash drive.
The power supply and all electronics are contained on a circuit
board supported on a new quick install chassis and housed in a
metal cabinet. Available accessories include local and remote
upload/download software, remote annunciators, and reverse polar-
ity/city box transmitter (4XTMF).
Features
• Listed to UL Standard 864, 10th edition
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele-
phone Service) Central Station Communicator over AlarmNet
• Optional CELL-MOD or CELL-CAB-FL GSM Central Station
Communicator over AlarmNet®
• Automated activation of the ECC-50/100 Emergency Command
Center
• ECC-FFT Firefighter Telephone option
• Compatible with SWIFT® wireless devices
• Auto-programming (learn mode) reduces installation time.
Reports two devices set to the same address
• Four built-in, independently programmable Style Z (Class A) or
Style Y (Class B) NAC circuits
• Selectable strobe synchronization for System Sensor, Wheelock,
and Gentex devices
• Notification Appliance Circuit End of Line resistor matching
• Four programmable function keys for ease of maintenance
• Two programmable relays and one fixed trouble relay
• Built-in Programmer
• Integral 80-character LCD display with backlighting
• Real-time clock/calendar with automatic daylight savings control
• History file with 1,000 event capacity
• Addressable sounder base compatibility
• Multi-criteria detector (smoke, heat, CO) with programmable
response
• Control module delay timer
• Automatic detector sensitivity testing (NFPA 72 compliant)
• Automatic device type-code verification
• Point trouble identification
• Waterflow selection per module point
• Alarm verification selection per detector point
Addressable Fire Alarm Control Panels
• Maintenance alert warns when smoke detector dust accumula-
tion is excessive
• One-person audible or silent walk test with walk-test log and
printout
• System alarm verification selection per detector point
• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA
72 compliant)
• Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
• Remote Acknowledge, Alarm Silence, Reset and Drill via
addressable modules or remote annunciator
• Upload/Download of program and data via USB with optional FS-
Tools Programming Utility
SLC COMMUNICATION LOOP
• Supports LiteSpeed™ and CLIP protocols
• SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with
twisted, unshielded wire
• Single addressable SLC loop which meets NFPA Class B and
Class A requirements
• 198 addressable device capacity (99 addressable detectors and
99 modules)
• Compatible with Fire•Lite's addressable devices (refer to the
SLC Wiring Manual)
NOTIFICATION APPLIANCE CIRCUITS (NACS)
• Two independently programmable output circuits. Circuits can be
configured for the following outputs:
– Style Y (Class B)
– Style Z (Class A)
• Silence Inhibit and Autosilence timer options
• Continuous, March Time, Temporal, or California code for main
circuit board NACs with two-stage capability
• Selectable strobe synchronization per NAC
• 2.5 A special application, 250mA regulated, total power for NACs
NOTE: Maximum or total 24VDC system power shared between all NAC
circuits and the ANN-BUS is 2.7 A
DF-60957:A