SYSTEM SETUP

1=TIMERS

2=NAC
3=RELAYS
System Setup Screen #2
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
MS-9050UD PN 52413:C 01/23/08
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will begin. In the
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and
2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows
the programmer to select the month that daylight savings time will end. In this sub-screen,
pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will end. In the first
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will
select the last week of the selected month.
3.6.5.4 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1
while viewing System Setup Screen #2. The following screen will be displayed:
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLOW
1=AC LOSS DELAY

3.6.5.4.1 PAS (Positive Alarm Sequence) Delay

The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180
seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The
following display will appear:
RANGE 0-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
TIMERS
000
000
000
Timer Screen #1
TIMERS
000
Timer Screen #2
PAS DELAY
PAS Delay Screen
Programming
93