Programming
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay).
When the second digit is entered, the display will return to AC Loss Delay Screen #1. Refer to the table on page 43 for permissible settings.
NOTE: Upon the loss of AC power at the control panel, relays programmed for 'AC Loss' will transfer immediately, regardless of the AC Loss
Delay setting. If no trouble exists at the panel other than AC Loss, the System Trouble relay and 4XTMF Form-C Trouble contact will delay its
activation for the duration of the AC Loss Delay setting.
Control Module Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
Timer Screen #2
A flashing cursor will appear in the lower left corner of the display. Type the three digit control module delay in seconds (00 to 180 second
delay). When the third digit is entered, the display will return to the Delay Screen which will indicate the new delay time. Refer to the table
on page 43 for permissible settings.
Control Module Auto Silence (Canadian Mode Only)
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
3=CTRL AUTO SIL. 000
Timer Screen #2
To disable the Auto Silence feature, press 1 for No while viewing Control Module Auto Silence Screen #1. To enable the Auto Silence fea-
ture, press the number corresponding to the time delay which will elapse before Control Module Auto Silence activates. This information
will be stored in memory and the display will return to Timer Screen #2.
In-Suite Silence (Canadian Mode Only)
TIMER
1=IN SUITE SIL.
2=SUITE RESOUND
Timer Screen #3
A flashing cursor will appear in the lower left corner of the display. Type the two digit in-suite silence delay in minutes (01 to 30 minute
delay). The default time is 30 minutes. When the second digit is entered, the display will return to the Delay Screen which will indicate the
new delay time.
NOTE: If the In-Suite Silence Timer is set shorter than the Silence Inhibit feature, the system will not silence.
72
RANGE 00-23 HOURS
The control module delay feature, if enabled, will delay activation of a control module after being triggered by
an alarm condition. Pressing 2 while viewing Timer Screen #2 will display the following:
The Control Module Auto Silence feature is only available when the FACP is in Canadian mode of operation.
When enabled, this feature automatically silences all silenceable control modules after a programmed length of
time. To enable this feature and program the time delay before Control Module Auto Silence activation, press 2
while viewing Timer Screen #2. The following screens will be displayed:
CTRL AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Control Auto Silence Screen #1
The In-Suite Silence feature is only available when the FACP is in Canadian mode of operation. When enabled,
30
this feature automatically silences all active outputs mapped to the In-Suite Silence Zone (as described in "Spe-
01
cial Purpose Zone" on page 65) after a programmed length of time. Pressing 1 while viewing Timer Screen #3
will display the following.
RANGE 1-30 MINUTES
AC LOSS DELAY
AC Loss Delay Screen #2
CTRL MOD DELAY
RANGE 00-180 SECONDS
Control Module Delay Screen
CTRL AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Control Auto Silence Screen #2
IN SUITE SILENCE
In Suite Silence Delay Screen
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
CTRL AUTO SILENCE
1=30 MINUTES
Control Auto Silence Screen #3