Product Description
Remote Sync Output - TB8
Remote power supply synchronization output
24 VDC nominal special application power
Maximum current is 350 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit
Programmable Class A or Class B wiring
Primary ANN-BUS - TB9
Class A or Class B wiring
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Class A wiring uses Terminal 3 (+/A Return) and Terminal 4 (-/B Return)
Annunciators require non-resettable power
Secondary ANN-BUS - TB10
Class B wiring only
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Annunciators require non-resettable power
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from
the FACP.
Special Application
Non-resettable or
Resettable Power
Special Application
Resettable or
Non-resettable Power
Special Application
Resettable or
Non-resettable Power
Synchronization
14
1.0 amp max
per circuit
1.0 amp max
per circuit
1.0 amp max
per circuit
NAC #1
3.0 amps max
per circuit
3.0 amps max
NAC #2
per circuit
NAC #3
3.0 amps max
per circuit
3.0 amps max
NAC #4
per circuit
Remote
0.35 amp max
per circuit
Output
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability
Standby
3.0 amps max
per panel
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Specifications
Alarm
8.0 amps max
per panel