Honeywell Fire-Lite Alarms ES-1000X Manual page 54

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
Select Pre-signal Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by assigning the same zone to it; in this example
Z001
Program an output, such as a control module, for Pre-signal activation by assigning zone Z254 to it. This control module may be
connected to a signaling device used to indicate a Pre-signal condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 254 and set the Pre-signal delay timer to some value
With the preceding program settings, when the detector with address 005 is activated, zone Z254 will cause its associated control module to
activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone
Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both
Zone Assignment
EDIT DETECTOR
1=ZONE ASSIGNMENT
000
Edit Detector Screen #4
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first 0 to the right. Enter the three digit number corresponding to the zone that is to
be assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones can
be left blank or programmed as general alarm zone Z000. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate through
the zones and the CLEAR key can be used to quickly clear a zone.
If the selected detector is a multi-criteria detector, the following screen will display respective before the Zone Assignment Screen allowing
the user to program the zones independently.
Wireless
EDIT DETECTOR
WIRELESS
2=SOUNDER BASE
3=NOT USED
Edit Detector Screen #5
Sounder Base
EDIT DETECTOR
WIRELESS
NO
2=SOUNDER BASE
Edit Detector Screen #5
If the selected detector has been installed in a sounder base, press 1 while viewing Sounder Base Screen #1 until the display reads Installed
Yes. Each press of the 1 key will cause the display to toggle between Installed Yes and Installed No.
The Silenceable selection allows the programmer to select whether the selected sounder base can be silenced, either by pressing the Alarm
Silence key or by enabling Autosilence. Pressing the 2 key while viewing Sounder Base Screen #1 will enable the Silenceable feature caus-
ing the display to read Silenceable Yes. Repeated presses of the 2 key will cause the display to toggle between Silenceable Yes and Silence-
able No. When set to Canadian mode of operation, a third silenceable option appears, Silenceable Auto. When set to Silenceable Auto, the
intelligent sounder base will automatically silence after the Control Module Auto Silence timer expires.
54
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while viewing Edit
Detector Screen #4 displays the following screen:
Multi-Criteria Detector Zones Screen
The Wireless selection will update automatically if the system recognizes a wireless device. A wireless device
NO
operates as part of the SWIFT wireless network. If the detector is wireless, the display reads Wireless Yes. If the
device is wired, the display will read Wireless No. Fore more information on the SWIFT wireless network, refer
to the SWIFT manual, #LS10036-000FL-E.
The Sounder Base selection allows the programmer to enter different values if the selected detector is mounted
in an addressable sounder base. Pressing 2 while viewing Edit Detector Screen #5 will display the following:
SOUNDER BASE
1=INSTALLED
2=SILENCEABLE
3=CODING
Sounder Base Screen #1
ZONE ASSIGNMENT
Z000
Zone Assignment Screen
EDIT DETECTOR
1=PHOTO ZONES
2=HEAT ZONES
3=CO ZONES
NO
YES
STEADY
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
SOUNDER BASE
1=ZONE ASSIGNMENT
2=VOLUME
LOW
Sounder Base Screen #2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-1000xcFire-lite alarms es-1000xi