Honeywell Fire-Lite Alarms ES-1000X Manual page 36

Addressable fire alarm control panel
Table of Contents

Advertisement

Installation
4.
Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual (refer
to "ANN-BUS Setup" on page 87).
Note that the Auto-configure feature allows the programmer to quickly bring all installed ANN-BUS modules online (refer to "Auto-
Configure" on page 93).
5.
Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 2.19). Only one printer can be connected.
Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6"W x 7-3/4"H x 1-7/16"D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
Connecting a PRN-7 Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire
Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may be
used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-9 cable. One end of the cable will plug into the
DB-9 connector on the PRN-7 printer and the other end plugs into the serial connector on the ANN-S/PG module.
Setting Printer Options
Refer to the documentation supplied with the PRN-7 printer for instructions on using the printer menu controls. Set the printer options (under
the menu area) as shown in the following table:
PRN-6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes within the control panel and time-stamps the
printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9" x 11" tractor-feed paper. This
section contains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire
Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may be
used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable. One end of the cable will plug into the
DB-25 connector on the PRN printer and the other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9
port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer cable. Connect either a
serial or parallel printer, but not both at the same time.
36
Option
Setting
Font
HS Draft
LPI
ESC Character
Bidirectional Copy
CG-TAB
Graphic
Country
E-US ASCII
Auto CR
Color Option
Not Installed
Formien
Lines
6LPI=60
Standard
Exec 10.5
Barcode
Barcode
Unsecured
Table 2.1 PRN-7 Setup Options
Option
CPI
6 LPI
Skip
ESC
Emulate
ON
I/O
Buffer
Serial
OFF
Baud
Format
Protocol
Character Set
SI.Zero
Off
Auto LF
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Optional Module Installation
Setting
10CPI
0.5
LQ-2550
64K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On