Important! The FACP will automatically reset 2 minutes after completion of a user program download. To prevent program corruption, the
operator must wait until this panel reset occurs before performing any panel operations.
CAUTION: After successfully downloading a program, make certain to perform the following steps:
1.
Print out all programmed data via Print Mode or manually view programmed entries and compare to intended program data
2.
Test all affected panel operations
3.
Immediately correct any problems found

7.1 USB Upload/Download

NFPA 72 requirements state that a technician be on-site and at the control panel whenever the FS-Tools Programming Utility is used to
download any information to the FACP. This applies to local and remote programming. For this reason, a new option has been added to the
FACP which allows an individual at the FACP to enter a password and either enable the proprietary mode where downloading will be
allowed at any time or access a specific password protected screen where downloading will be allowed regardless of the current proprietary
setting.
The USB upload/download option allows for the transfer of programming information via a flash drive. The USB thumb drive must be in
FAT32 file system format. This is typically the default format. Insert a USB flash drive into J20 on the bottom edge of the fire panel's circuit
board. The USB Download option can be selected from the main menu screen after successful login as shown below:
Select 2 to login to the panel.
Select 2 to login as a User.
Select the appropriate User login ID:
Enter the User's Master level password. Only a user with master level programming rights can access USB Up/Downloads. The following
screen will appear:
Pressing 3 for USB Up/Download while viewing the main menu will cause the following screen to be displayed:
Pressing 1 for Upload Program, while viewing the USB Up/Download screen, will display the following.
Using the keypad and arrow keys, enter a name for the current FACP configuration to save to the USB drive, and then press Enter.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023

Section 7: USB Upload/Download

MAIN MENU
1=READ STATUS MODE
2=LOGIN
SELECT ACCOUNT
1=ADMINISTRATORS
2=USERS
3=NOT USED
SELECT USER
1=USER 1
2=USER 2
3=USER 3
LOGIN FOR USER X
ENTER PASSWORD
MASTER MENU
1=PROGRAMMING MODE
2=FS-TOOL UP/DWNLOAD
3=USB UP/DOWNLOAD
USB UP/DOWNLOAD
1=UPLOAD CONFIG
2=DOWNLOAD CONFIG
UPLOAD TO USB
FILENAME: