Operating Instructions
4.23.4 Timers
Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be displayed:
These screens will indicate the delay time, in seconds, for each of the first three and last possible delay options. The AC Loss Delay time is
displayed in hours.
4.23.5 NACs
Each NAC can be programmed individually with unique settings with the exception of Canadian Mode. When the Canadian Option is
selected in programming (see "Canadian Option" on page 76), all NAC settings are changed to that of NAC 1. While in Canadian Mode, if
any NAC is setting is changed, all other NACs will get those same settings. Pressing 3 while viewing Read Status Screen #2 will display the
following screen:
The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed options for NAC 2, 3 to view the pro-
grammed options for NAC 3, or 4 to view the programmed options for NAC 4. The resulting screens will display the following information:
•
Enable/Disable Status
•
Circuit Type (Bell, Strobe, etc.)
•
Silenceable/Non-silenceable
•
Auto Silence Enable/Disable and time delay (in minutes)
•
Coding Selection (Temporal, Steady, etc.)
•
Zone Assignments
•
Silence Inhibit Enabled/Disabled
•
Synchronization Type (System Sensor, Wheelock, or Gentex)
•
MNS Override Enabled/Disabled
•
MNS Active Yes/No
4.23.6 Relays
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
The operator can view the programmed option for each relay by pressing the corresponding number key.
4.23.7 Program Check
Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be displayed:
Pressing 1 while viewing Program Check screen will display a screen which will indicate if any input zones have not been programmed to
one of the Notification Appliance Circuits. Use the up and down arrow keys to view all NACs.
Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any output zones have not been programmed
to at least one input zone. Use the up and down arrow keys to view all zones.
Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed
to at least one output zone. Use the up and down arrow keys to view all zones.
112
TIMERS
PAS DELAY
000
PRE SIGNAL
000
WATERFLOW
000
1=NAC 1
2=NAC 2
Pressing 1 while viewing Read Status Screen #3 will display the following screen:
1=RELAY 1
2=RELAY 2
3=RELAY 3
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
TIMERS
AC LOSS DELAY
CTRL MOD DLY
NAC
3=NAC 3
4=NAC 4
RELAYS
PROGRAM CHECK
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Read Status
02
000