Programming

Charger Enable

SYSTEM SETUP
1=CHARGER ENAB
2=BAT SIZE 18-26
3=NOT USED
System Setup Screen #6

Battery Size

The panel needs to be programmed to recognize the size of the battery in the system. The FACP cabinet can house two 26 Amp Hour batter-
ies. Batteries larger than 26 Amp Hour require a separate battery box. The minimum battery size for the ES-1000X panel is 18 Amp Hour.
Choose the corresponding number for the value of the battery in the system. Refer to Section 9.4 to determine system battery requirements.
3.5.6 History
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3

View Events

HISTORY
1=VIEW EVENTS

2=ERASE HISTORY

History Screen
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to view other events. Use the up and down
arrow keys to scroll through all of the displayed events.
Erase History
The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history file
to track future events. Pressing 2 while viewing the History Screen will display the following screen:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as fol-
lows:
After the History file has been erased, the display will return to the History Screen.
78
When using an external battery charger, the FACP battery charger must first be disabled. Pressing 1 while view-
YES
ing System Setup Screen #5 will cause the display to toggle to Charger Enab No, which will allow the use of an
AH
external battery charger. Each press of the 1 key will cause the display to toggle between Charger Enab Yes and
Charger Enab No.
The History option allows an authorized user to view or erase events which have occurred in the control panel.
Pressing 1 while viewing Programming Screen #3 will display the History options as shown in the following
display:
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illustrated in
the following:
BATTERY SELECTION
1=18-26
AMP HOUR
2=33-55
AMP HOUR
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023