Optional Module Installation
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate a trouble condition by NOT turning on its
AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that
the FACP will provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-80 at
the FACP.
ANN-100 Remote Fire Annunciator
Specifications
Operating Voltage: 24 VDC
Current
– Standby: 20 mA
– Alarm: 25 mA
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface or Flush-mount
Dimensions: 12-1/4"W x 11-1/2"H x 7/8"D (31.1 cm W x 29.2 cm H x 2.2 cm D)
For indoor use in a dry location only
The following table shows the ANN-100 connections to the ES-1000X.
Programming
Following installation and wiring of the ANN-100 LCD annunciator to the FACP, the annunciator must be added to the system via FACP
programming. Refer to the programming section titled "ANN-BUS Setup" on page 87 in this manual for detailed programming information.
Trouble Response
If the ANN-100 is installed but the ANN-BUS is not enabled at the FACP, the ANN-100 will indicate a trouble condition by NOT turning on
its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that
the FACP will provide no indication of an ANN-100 trouble.
To clear the ANN-100 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-100 at
the FACP.

ANN-S/PG Serial/Parallel Interface Module

Installation
1.
Ensure that all power (AC and DC) has been removed from the FACP.
2.
Connect the ANN-S/PG to the FACP as illustrated in Figure 2.19
3.
Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
ES-1000X
Terminal GND (-) on TB11
Terminal PWR (+) on TB11
Terminal Data (A) on TB9
Terminal Data (B) on TB9
ANN-BUS and DC power wiring are
supervised and power-limited
24 VDC
Primary
non-resettable
ANN-BUS
ES-1000X
Figure 2.19 ANN-S/PG Connection to FACP
ANN-100 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
cable connectors for
connection to printer
ANN-S/PG Module
Installation
Parallel
Serial
35