Master Programming Level
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian specifications.
The Positive Alarm Sequence and Pre-Signal option are not available for Canadian applications.
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
The F2 function key is automatically configured to perform an automatic alarm signal cancel in two-stage NAC operation when
pressed. This prevents the NAC from advancing to the second-stage alarm.
The F3 function key is automatically configured to force active two-stage NACs into the second (alarm) stage.
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
AlarmNet supervision settings for Ethernet communications are fixed at 3 minutes and cannot be changed regardless of programming
selection.

Waterflow Silenceable

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO

3=MNS OVERRIDE

System Setup Screen #3
MNS Override
This feature is not available at this time.

Auxiliary Power

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM

3=LANGUAGE

ENGLISH
System Setup Screen #4
Select the desired output. The following screen will be displayed.
Only Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press 1. Each press of the 1 key will cause the dis-
play to toggle between Class A Yes and Class A No.
Each output can be programmed as resettable or non-resettable power. Non-resettable power is suitable for powering annunciators while
resettable power is suitable for powering smoke detectors. Each press of the 2 key will cause the display to toggle between Resettable Yes
and Resettable No.

Trouble Reminder

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4
Language
The language option is used to change the text on the panel display to either English or French. Pressing the 3 key will cause the display to
offer a choice of 1=English and 2=French.

4XTMF Supervision

SYSTEM SETUP
1=4XTM SPV ENAB
2=REM SYNC ENAB
3=NOT USED
System Setup Screen #5

Remote Sync Enable

Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly
the same time. Refer to Section 2.5, "Remote Synchronization Output", on page 26 for more information. To enable remote synchronization,
press the 3 key while viewing System Setup Screen #5. Each press of the key will toggle the screen between Rem Sync Enab Yes and Rem
Sync Enab No.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the system for
silenceable on non-silenceable waterflow circuits. Each press of the 2 key will toggle the display between
Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all output devices associated with
NO
a waterflow type input device, will be non-silenceable. When Waterflow Sil. Yes is selected, all output devices
associated with a waterflow type input device, will be silenceable.
Three Special Application 24 VDC power outputs are available at TB11, TB18, and TB13 on the upper right
corner of the main circuit board. Pressing 3 while viewing System Setup Screen #4 displays the following:
24HR
The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for alarms and trou-
bles, after the panel has been silenced. Refer to "System Setup" on page 67, for a detailed description of this
24HR
feature. Pressing 2 while viewing System Setup Screen #4 will cause the display to toggle to Trouble Rem 4 or
Trouble Rem 24, which enables this feature for resound at either 4 or 24 hours, respectively. Refer to the table
on page 43 for permissible settings.
If a 4XTMF Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing 2 while viewing System Setup Screen #5 will cause the display to toggle to 4XTM Supv Enab. Yes,
NO
YES
which means there is a 4XTMF installed. Each press of the 2 key will cause the display to toggle between
4XTM Supv Enab. No and 4XTM Supv Enab. Yes. Refer to the table on page 43 for permissible settings.
AUX POWER
1=AUX 1
2=AUX 2
3=AUX 3
AUX#
1=CLASS A
YES
2=RESETTABLE
YES
Programming
77