Programming
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen similar to one of the following two screens to
be displayed:
If there are no events in the current walktest session, the first screen will be displayed, indicating no events have been stored in the walktest
log. If any events have been stored, a screen similar to the second will be displayed indicating the latest event. As walktest events occur, the
display will change to indicate the latest event. All stored events can be scrolled on the screen by pressing the up or down arrow keys. To
return to the first event, press the 1st Event key.
Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the following screens:
If the system has no points installed, the first screen will be displayed. If points are installed, the second screen will be displayed, which
allows the viewing of all untested system points and their status relating to the current walktest session. The up and down arrow keys will
allow viewing of all untested points. If a point is tested while it is being displayed, the screen will update and display the next untested point.
The first line indicates the total number of untested points. The second line displays information about an untested point. A description on
the bottom of the screen will indicate if the displayed point has been disabled, if the Walktest option has been disabled for that point or if the
point is not yet tested. The up and down arrow keys allow the user to scroll through all untested points.
Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen which will show a total of the tested detec-
tors, tested modules, untested detectors and untested modules for the current walktest session.
To end the Walktest session, press the Escape key to return to the Walktest screen. Pressing 3 for View Results while viewing the Walktest
screen, after a walktest session has been completed, will allow the operator to view the final results of the most recent walktest.
3.6.5 System
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
SYSTEM
1=NACS
2=REM SYNC ENAB
3=NOT USED
System Screen #1
Pressing 1 while viewing NAC Screen #1 will cause the display to change to NAC1 N. This will deactivate the devices on the main circuit
board's selected NAC output. Each press of the 1 key will cause the display to toggle between NAC1 N and NAC1 Y. The same action is per-
formed for the other 3 NAC circuits by selecting the number of the desired output circuit.
To enable remote synchronization, press the 2 key while viewing System Screen #1. Each press of the key will toggle the screen between
Rem Sync Enab Yes and Rem Sync Enab No.
SYSTEM
1=TIME/DATE
2=CHARGER ENB
3=4XTM SUPV ENB
System Screen #2
To change the time, press 1 to display the following screen:
100
NO EVENTS IN
WALKTEST LOG
NO POINTS IN
SYSTEM
Pressing 2 while viewing Maintenance Screen #2, will display the following screen:
SYSTEM
1=NACS
2=REM SYNC ENAB YES
3=NOT USED
System Screen #1
Pressing 1 while viewing System Screen #1 will display the following:
YES
Pressing 1 while viewing System Screen #2 will cause the following screen to be displayed:
NO
NO
ALARM: MONITOR
OR
10 15A 050417 1M006
UNTESTED POINTS
1D001
OR
NOT TESTED
ENABLE NACS
1=NAC1
Y
3=NAC3
2=NAC2
Y
4=NAC4
Disable NACs Screen
TIME AND DATE
1=TIME
09:28 AM
2=DATE
12-18-2022
3=CLOCK FORMAT 12HR
Time and Date Screen
ENTER TIME
09:28 AM
1=AM
2=PM
Time Screen
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Maintenance Programming Level
NORTH CLASSROOM
Z001
010
SMOKE (PHOTO)
SYSTEM
1=TIME/DATE
2=CHARGER ENAB
YES
3=4XTM SPV ENB
NO
System Screen #2
Y
Y