The ES-1000XC is supplied standard with a dress panel for Canadian applications.
•
When installing and programming the FACP, the Canadian Option must be set to ON prior to any other panel programming (refer to
"Canadian Option" on page 76 of the Programming Section of this manual).
•
At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary operator interface. Wiring to the ANN-LED
must be in metal conduit and must be connected to the FACP's Primary ANN-BUS.
•
If remote indicators are desired, they must be connected to the Secondary ANN-BUS circuit.
•
The installer must write in the Date of Final Assembly on the Master Marking and Warranty Label located on the FACP backbox door.
•
Positive Alarm Sequence (PAS) and the Pre-Signal option are not available for Canadian applications.
•
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
•
The F2 function key is automatically configured to perform an automatic alarm signal cancel in two-stage NAC operation. This
prevents the NAC from advancing to the second-stage alarm.
•
The F3 function key is automatically configured to force active two-stage NACs into the second (alarm) stage. It advances NAC coding
directly to the second stage alarm.
•
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
•
AlarmNet supervision settings for panels communicating in Ethernet-only method are fixed at 3 minutes and cannot be changed
regardless of programming selection.
158
Appendix J: Canadian Applications
Optional Secondary ANN-BUS (data on connector
TB10, power on TB18 with power programmed as
Primary ANN-BUS (data
on connector TB9, non-
resettable power on
TB11) in metal conduit
(adjacent to FACP)
FACP
FIRE SYSTEM
ALL
ACTIVE
CALL
1
13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
23
12
24
®
FI
LIT
AL
by Honeywell
optional
ECC-50/100
audio system
Figure J.1 FACP Minimum Configuration - Single ANN-LED
non-resettable)
ANN-LED
SYSTEM
CONTROL
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
ANN-LED
ANN-100
ANN-I/O
ANN-S/PG
ANN-RLY