Maintenance Programming Level
A flashing cursor will appear on the left side of the display. Enter the four digit number corresponding to the time (0000 - 1259). When the
fourth digit is entered, the cursor will move one position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display
will return to the Time and Date Screen displaying the new time.
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be displayed:
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit day and two digit year. The cursor will move
one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date
Screen which will show the new date.
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time and Date screen
will cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display
purposes only).
SYSTEM
1=TIME/DATE
2=CHARGER ENAB
3=4XTM SPV ENAB
System Screen #2
3.6.6 Zone Setup
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
Pressing 1 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To enable a zone, enter the three digit zone number (000 - 255). After the third digit is entered,
the zone will be enabled and the cursor will return to the original position. The next zone to be enabled can then be entered. Press Esc
(Escape) to return to the previous screen.
Pressing 2 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To disable a zone, enter the three digit zone number (000 - 255). After the third digit is
entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered. Press
Esc (Escape) to return to the previous screen.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
To enable the onboard battery charger, press the 2 key while viewing System Screen #2. Each press of the key
will toggle the screen between Charger Enab Yes and Charger Enab No. The setting must say Charger Enab
YES
No when an external battery charger is being used.
NO
If a 4XTMF Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing 3 while viewing System Screen #2 will cause the display to toggle to 4XTM Spv Enab. Yes, which
means there is a 4XTMF installed. Each press of the 1 key will cause the display to toggle between 4XTM Spv
Enab. No and 4XTM Spv Enab. Yes.
Pressing 3 while viewing Maintenance Screen #2 will display the following screen:
ENTER DATE
MONTH DAY YEAR
12-18-22
Date Screen
ZONE SETUP
1=ENABLE
2=DISABLE
Zone Setup Screen
ZONE TO ENABLE
Z
Enable Screen
ZONE TO DISABLE
Z
Disable Screen
Programming
101