Section 3: Programming - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:
Permitted in
Program feature or
ULC-S527
option
/ULC-S559?
Pre-Signal Delay Timer
AC Fail Delay Timer
Canadian Option
N (UL864)
Y (ULC-S527)
Y (ULC-S559)
Control Module Delay
Silence Inhibit Timer
Trouble Reminder
(when used with SWIFT
wireless devices)
4XTMF Supervision
Supervised Phone Line
Ethernet Fault
Test Time Interval
Ethernet Supervision
Options
Trouble Call Limit
Annunciator Lock Enable
Remote Download
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023

Section 3: Programming

UL864/
(Y/N)
Y
Refer to "Pre-signal Delay" on page 71.
• 0-180 seconds
Y
Refer to "AC Loss Delay" on page 71.
• 0-23 hours
Refer to "Canadian Option" on page 76.
• On
• Off
N
Refer to "Control Module Delay" on page 72.
• Control Module Delay = 0 (factory default): no delay in Control
Module activation
• Control Module Delay = 1-180: delays control module
activation from 1-180 seconds
Y
Refer to "Silence Inhibit" on page 75.
• Silence Inhibit Yes/Silence Inhibit No
• 0-300 seconds (in Canadian mode)
Y
Refer to "Trouble Reminder" on page 77
• 4 hours
• 24 hours
Y
Refer to "4XTMF Supervision" on page 77.
• Enabled Yes
• Enabled No
Y
Refer to "Supervised Phone Line" on page 79.
• Supervised Yes
• Supervised No
Y
Refer to "Ethernet Fault" on page 81.
• 1-60 minutes
Y
Refer to "Test Time Interval" on page 82.
• 24 hours
• 12 hours
• 8 hours
• 6 hours
• 4 hours
• 3 hours
• 2 hours
• 1 hour
Y
Refer to "Supervision Settings" on page 83
• NFPA 2010 Dual Path: Supervision Interval: 24 Hours
• NFPA 2010 Sole Path: Supervision Interval: 5 min
• NFPA 2013 Dual Path: Supervision Interval: 6 Hours
• NFPA 2013 Sole Path: Supervision Interval: 1 Hour
N
Refer to "Trouble Report Limit (Dialer Runaway Prevention)" on
page 83.
• Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
• Trouble Call Limit = 1 - 99: limits call for each unique trouble to
from 1 to 99 within a 24 hour period
Y
Refer to "Lock Enable Option" on page 95.
• Enabled Yes
• Enabled No
Y
Refer to "FS-Tools Upload/Download" on page 119.
• Remote Download - Proprietary No
• Remote Download - Proprietary Yes
Possible settings
Settings permitted in
UL864 / ULC-S527/ULC-S559
60-180 seconds
1-3 hours
Off (UL864)
On (ULC-S527)
On (ULC-S559)
Control Module Delay = 0 for no delay in
control module activation
Any setting is permitted for UL864.
For ULC applications, the timer must be
set to 300 seconds.
4 hours
Enabled Yes when the 4XTMF module is
installed.
Supervised Yes if transmission method
is POTS.
1 minute
• 6 hours
• 4 hours
• 3 hours
• 2 hours
• 1 hour
For UL864 applications:
• 5 min
• 6 hours
• 1 hour
For ULC applications, the supervision
interval for panels communicating in
Ethernet-only method is fixed at 3
minutes and cannot be changed,
regardless of setting option, when the
Canadian Option is enabled.
Trouble Call Limit = 0 for unlimited
Central Station trouble calls
Enabled Yes
Remote Download Proprietary Yes for
Proprietary system intended to protect
only contiguous properties
43