Honeywell Fire-Lite Alarms ES-1000X Manual page 64

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Adjective/Noun Screen
1=NORTH
2=SOUTH
3=EAST
Adjective Screen #1
1=3RD
2=4TH
3=5TH
Adjective Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Adjective/Noun Screen
1=BASEMENT
2=BOILER RM
3=CLASSROOM
Noun Screen #1
1=KITCHEN
2=LOBBY
3=OFFICE
Noun Screen #5
Pressing 3 or 4 while viewing the Adjective/Noun Screen will display screens similar to the previous Adjective and Noun Screens. The new
screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the FS-Tools programming utility.
Description
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Control Screen #4
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device
being programmed. This information will appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the
appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 1, A, and B. Press the right arrow key to move the cursor one position to the right and repeat the pro-
cess to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all char-
acters have been entered, press the Enter key to store the information. The display will return to the Edit Control Screen #4, displaying the
new information at the bottom of the screen.
MNS Override
This feature is not available at this time.
Control Module Delay
EDIT CONTROL
1=MNS OVERRIDE
2=CTRL MOD DLY
Edit Control Screen #5
64
Pressing 1 while viewing the Adjective/Noun Screen will cause the following screen(s) to be displayed. Note
that the keypad down arrow key must be pressed to see all the Adjective screens. Press the number correspond-
ing to the adjective that is to be used as a descriptor for the location of the control module currently being pro-
grammed.
1=WEST
2=FRONT
3=CENTER
Adjective Screen #2
1=FLOOR 1
2=FLOOR 2
3=FLOOR 3
Adjective Screen #6
Pressing 2 while viewing the Adjective/Noun Screen will cause the following screen(s) to be displayed. Note
that the keypad down arrow key must be pressed to see all the Noun screens. Press the number corresponding to
the noun that is to be used as a descriptor for the location of the control module currently being programmed.
1=CLOSET
2=CORRIDOR
3=ELECTRIC RM
Noun Screen #2
1=PATIENT
2=RESTROOM
3=ROOM
Noun Screen #6
The Description selection allows the programmer to enter additional information about the control module cur-
rently being programmed. This information will be displayed as part of the device label on the display. Pressing
2 while viewing Edit Control Screen #4 will cause the following screen to be displayed:
DESCRIPTION
ADJECTIVE/NOUN
The control module delay feature, if enabled, will delay activation after being triggered by an alarm condition.
NO
Pressing 2 while viewing Edit Control Screen #5 will cause the display to change from the factory default of
NO
Ctrl Mod Dly No to Ctrl Mod Dly Yes. Each press of the 1 key will cause the display to toggle between the two
options. Delay time varies from 0-180 seconds. See "Control Module Delay" on page 72 to set the delay time.
The control module must first be set to Silenceable No to enable the Delay Timer.
1=REAR
2=UPPER
3=LOWER
Adjective Screen #3
1=FLOOR 4
2=FLOOR 5
3=ROOM
Adjective Screen #7
1=ELEVATOR
2=ENTRANCE
3=FLOOR
Noun Screen #3
1=STAIRWAY
2=STOREROOM
3=WING
Noun Screen #7
1M002
Adjective/Noun Screen
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
1=MAIN
2=FIRST
3=2ND
Adjective Screen #4
1=GARAGE
2=HALLWAY
3=HVAC RM
Noun Screen #4
1=ZONE