1=Autoprogram - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
Select the appropriate User login ID:
Enter the User's Master level password. Only a user with master level programming rights can access panel programming. The following
screen will appear:
Select 1 to access panel programming mode.
Pressing the down arrow will display more programming options:
1=LOOP SETUP
2=SYSTEM SETUP
3=NOT USED
Programming Screen #2
3.5.1 Autoprogram
PROGRAMMING

1=AUTOPROGRAM

2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device
installed on the SLC loop. While autoprogramming, the panel will display the following:
When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop(s) simi-
lar to the following display:
In the preceding example, the display indicates that this SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules
installed.
Pressing the ESC key will return the display to Programming Screen #1.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
PROGRAMMING
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the con-
trol panel to poll all devices installed on the SLC loop(s). The primary purpose of autoprogramming is to allow
the installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is
powered-up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default values for
LOGIN FOR USER X
ENTER PASSWORD
MASTER MENU
1=PROGRAMMING MODE
2=FS-TOOL UP/DWNLOAD
3=USB UP/DOWNLOAD
PROGRAMMING
1=AUTOPROGRAM
2=POINT SETUP
3=ZONE SETUP
Programming Screen #1
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Programming
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-1000xcFire-lite alarms es-1000xi

Table of Contents