Programming
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * = Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from
000 - 255)
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module and 002 = Module Address 02)
To change the programming for the displayed module, press the keypad down arrow key to view the following Edit Control screens:
EDIT CONTROL
1MOO2
ENABLED
YES
2=TYPE CONTROL
3=SILENCEABLE
Edit Control Screen #2
Enabled/Disabled Module
EDIT CONTROL
ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
Control Type
EDIT CONTROL
ENABLED
2=TYPE CONTROL
3=SILENCEABLE
Edit Control Screen #2
While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad
number key. The display will return to the Edit Control Screen #2 and indicate the new type selection.
NOTE: A control relay module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control
relay module is disabled.
62
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
YES
000
Edit Control Screen #3
The system will show whether the control module is enabled or disabled. To change the status of the module,
YES
the programmer must enter system programming using a Maintenance password.
To select the type of control module being programmed, press the 2 key while viewing the Edit Control Screen
YES
#2. This will cause the control panel to display the following Control Type Screens. Press the down arrow key
to view additional screens and selections.
EDIT CONTROL
YES
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Control Screen #4
CONTROL TYPE
1=NOT USED
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
EDIT CONTROL
1=MNS OVERRIDE
NO
2=CTRL MOD DLY
NO