Installation
Mounting/Installation
The ANN-LED Module is supplied with a metal backbox, mounting bracket, and cover. The ANN-LED must be mounted within 20' (6.1m)
of the FACP in the same room and wired in conduit. Refer to the ANN-LED Installation Document #53032 for more information.
ANN-LED Board Layout and Connection to FACP
Figure 2.25 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for
selecting the ANN-BUS ID number.
ANN-RLY Annunciator Module
Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Operating Temperature: 32°F to 120°F (0°C to 49°C)
•
For indoor use in a dry location only
40
Figure 2.24 Exploded View of ANN-LED
ANN-BUS (ID#)
Address DIP switch
Primary ANN-BUS
+24 VDC
Figure 2.25 ANN-LED Board Layout and Connection to FACP
ANN-LED
ANN-BUS and DC power wiring
are supervised and power-limited
-24 VDC
ES-1000X
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023