Programming
If the selected address has been added to programming and a module (such as a monitor module) with the selected address is physically
installed on the SLC and is communicating with the control panel, the following screen will be displayed:
To change the programming for the displayed module, press the keypad down arrow key to view the following Edit Monitor screens. In the
preceding example:
Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control
panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been programmed, describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from
000 - 255)
1M012 - represents the Loop, Device type and Device address (1 = SLC Loop, M = Module and 012 = Module Address 012)
W or * - indicates whether or not the device is programmed for Walktest (W = programmed for walktest, * = not programmed for
walktest).
X or * - indicates whether or not the device is wireless (X = wireless, * = wired).
If the selected address corresponds to a control module, a screen displaying information about the control module with the selected address
will be displayed as shown in "Edit Module Screen for Control Modules" on page 61.
If the selected address corresponds to a monitor module, a screen displaying information about the module with the selected address will be
displayed as illustrated in the following:
EDIT MONITOR
1M012
ENABLED
YES
2=TYPE MONITOR
Edit Monitor Screen #2
Enabled/Disabled Module
EDIT DETECTOR
ENABLED
2=TYPE
Edit Detector Screen #2
Type Monitor
EDIT MONITOR
1=ENABLED
2=TYPE
MONITOR
Edit Monitor Screen #2
Pressing the down arrow key will display additional Monitor Type screens. While viewing one of the Monitor Type screens, select the type
of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Monitor Screen
#2 which will show the new type selection.
Table 3.1 lists the Monitor Types and their respective functions.
58
EDIT MONITOR
1=PRE-SIGNAL
WIRELESS
Edit Monitor Screen #3
The system will show whether the module is enabled or disabled. To change the status of the module, the pro-
YES
grammer must enter system programming using a Maintenance password.
Using the FS-Tools Upload/Download utility, unique user-defined monitor types can be created and loaded into
the FACP for later use. The FACP response to the activation of a user-defined type is the same as most previous
standard types in the list, thus allowing a variety of user-defined types and responses. To select the type of mon-
itor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2. This will cause the
control panel to display the following Monitor Type Screens:
1=PULL STATION
2=USER-DEFINED-1
3=WATERFLOW
Normal MONITOR
<ADJ><NOUN>
ZNNN
W 1M012
Normal MONITOR
<ADJ><NOUN>
ZNNN
W
1M012
EDIT MONITOR
1M012
1=WALKTEST
NO
2=ZONE ASSIGNMENT
NO
000
Edit Monitor Screen #4
MONITOR TYPE
Monitor Type Screen #1
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
EDIT MONITOR
1M012
1=ADJECTIVE/NOUN
YES
2=DESCRIPTION
Edit Monitor Screen #5
1M012