9: Password Change - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
ANN-80/100 Options
XXX ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed ANN-80 or ANN-100 module will ever
sound. Pressing 1 while viewing the ANN-80/100 Options Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo
Enable No.
The Lock Enable option allows the programmer to select whether or not any installed ANN-80 or ANN-100 annunciator must be unlocked
by its key before any annunciator key presses will function. Pressing 2 while viewing the ANN-80/100 Options Screen #1 causes the display
to toggle between Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock position is ignored). This
option is not available in Canadian applications. Refer to the table on page 43 for permissible settings.
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select whether the Ack/Step button on any installed
ANN-80 or ANN-100 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80/100 Options Screen
#1 causes the display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button
never functions). In Canadian mode, the FACP cannot be controlled by the ANN-100 so the Reset feature is unavailable. This option is
called STEP ENABLE in Canadian applications. Enabling the Step feature will allow the user to scroll through events on the screen.
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed ANN-80
or ANN-100 annunciator will function normally or always be ignored. Pressing 1 while viewing the ANN-80/100 Options Screen #2 causes
the display to toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed ANN-80 or
ANN-100 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80/100 Options Screen #2 causes the
display to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never functions). In
Canadian mode, the Reset feature is unavailable. The programming option will change to LMP BTN ENABLE in Canadian applications.
Pressing 2 while viewing the ANN-80/100 Options Screen #2 causes the display to toggle between Lmp Btn Enable Yes (the ANN-100 will
perform a local test of all LEDs) and Lmp Btn Enable No.
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the Drill button on any installed ANN-80 or
ANN-100 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80/100 Options Screen #2 causes the
display to toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never functions). In
Canadian mode, the Drill feature is unavailable. The programming option will change to SND BTN ENABLE in Canadian applications.
Pressing 3 while viewing the ANN-80/100 Options Screen #2 causes the display to toggle between Snd Btn Enable Yes (the ANN-100 will
perform a test of its local sounder by turning it on for 5 seconds) and Snd Btn Enable No.
Key Control Enable (Canadian Mode Only)
XXX ANN-BUS
1=KEY CTRL ENABLED
ANN-BUS Options Screen #2
3.5.9 Password Change
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Enter the current password and the new password. Note that the passwords will not be displayed on LCD annunciators.
The following screen will appear to verify the password change:
Re-enter the new password to accept the change. A message will appear showing the password has been successfully changed.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Pressing 3 while viewing the ANN-BUS screen will display the following screen:
ANN-80/100 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE YES
ANN-80/100 Options Screen #1
The Key Control feature is only available when the FACP is in Canadian mode of operation. Canadian mode
usually limits the functionality of annunciators. Enabling key control allows annuciator key presses to be pro-
cessed normally. To enable the annunciator Key Control, press 1 while viewing ANN-BUS Options screen #2
so that the display reads Key Ctrl Enabled Y. Each press of the 1 key will cause the display to toggle between
Key Ctrl Enabled Y and Key Ctrl Enabled N.
The user password, which has been assigned by the administrator, can be changed by selecting the Password
Change option. Pressing 1 while viewing Programming Screen #4 will cause the following screen to be
displayed:
MODIFY USER X
ENTER PASSWORDS
USER X:
Change Password Screen
MODIFY USER X
VERIFY PASSWORD
ANN-80/100 OPTIONS
1=SIL BTN ENABLE YES
YES
2=RST BTN ENABLE YES
YES
3=DRL BTN ENABLE YES
ANN-80/100 Options Screen #2
NEW:
NEW:
Programming
95