Honeywell Fire-Lite Alarms ES-1000X Manual page 75

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
4.
Any NACs currently in 1st stage activation will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in
2nd stage activation.
5.
If an F3 button in pressed, the NACs will progress to the second stage.
6.
If another alarm point is activated and the countdown timer is counting, the alarm point will have no effect on the NACs unless the
alarm point's zones are directly mapped to one of the NACs, in which case it will follow the procedure outlined in step 2.
7.
If another alarm point is activated and the countdown timer has stopped counting due to the Acknowledge switch being pressed, the
countdown timer will restart and the NACs will respond as outlined in step 2. NACs already in 2nd stage activation will not be affected.
8.
Any control modules assigned to special Zone 255 will be activated either by direct mapping of an input device programmed to Zone
255 or if the timer counts down to zero or when any NAC goes into 2nd stage coding.
9.
Control modules that are programmed to the same zone as the activated input device will not be delayed for activation.
Zone Assignment
NAC #
1=ZONE ASSIGNMENT
000
2=SILENC INHIBIT NO
NAC Screen #3
Note that Z*** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is Z000
for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to
be assigned to this NAC. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones can be
left blank or programmed as general alarm zone Z000. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the NAC Screen #3 which will show the zone assignments just entered.
Silence Inhibit
NAC #
1=ZONE ASSIGNMENT
000
2=SIL. INHIBIT
NAC Screen #3
Inhibit is programmable from 0-300 seconds. Pressing 2 while viewing NAC Screen #3 in Canadian mode only, will display the following:
A flashing cursor will appear in the lower left corner of the display. Type the three digit in suite silence delay in seconds (000 to 300 second
delay). The default time is 300 seconds. When the third digit is entered, the display will return to the NAC Screen #3 which will indicate the
new Silence Inhibit time.
Sync Type
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
3=MNS ACTIVE
NAC Screen #4
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock, and 3 will select Gentex.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 3.0 amps. Refer to the manufacturer's documentation supplied
with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded. To ensure
proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit.
MNS Override
This feature is not available at this time.
MNS Active
This feature is not available at this time.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while viewing NAC
Screen #3 displays the following screen:
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for a
period of five minutes. Resetting the FACP will also be prevented for one minute while the NAC programmed
for silence inhibit is activated. Pressing 2 while viewing NAC Screen #3 will cause the display to change from
NO
the factory default of Silence Inhibit No to Silence Inhibit Yes. Each press of the 2 key will cause the display to
toggle between the two options. If the panel is set to Canadian mode of operation, the duration for Silence
If synchronized strobes were selected as the Type of device installed, the type of synchronization must be
S
selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following screen to be dis-
NO
played:
NO
ZONE ASSIGNMENT
Z000
Zone Screen
NAC SILENCE INHIBIT
RANGE 0-300 SECONDS
NAC Silence Inhibit Screen
NAC SYNC TYPE
1=SYSTEM SENSOR
2=WHEELOCK
3=GENTEX
Programming
75