Master Programming Level

ANN-BUS Setup

ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciators Screen #1
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To enable the ANN-BUS, press 1 while viewing
ANN-BUS screen #1 so that the display reads ANN XXX Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN
XXX Enabled Yes and ANN XXX Enabled No.
Modules Installed
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #1
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more
addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen will be
displayed for each address:
Pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80 MODULE
3=ANN-100 MODULE
Press the number corresponding to the module/device type that is installed with the selected address.
NOTE: If the module type selected is the ANN-80, ANN-100, ANN-S/PG, or if Not Installed is selected, the ANN-BUS Address Screen shown
on the previous page will be displayed following the module selection. The options selected for each of these modules will be the same for all
modules of the same type (refer to "ANN-S/PG (Print) Options" on page 94 and "ANN-80/100 Options" on page 95).
If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed:
Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS
Address Screen will display the available options as described below.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Two ANN-BUS circuits are available on the ES-1000X. Press 1 to configure the Primary ANN-BUS or press 2
to configure the Secondary ANN-BUS. The following screens will be displayed for either ANN-BUS circuit
where (XXX) indicates either Primary or Secondary..
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
If an ANN-BUS module is installed, press 2 for Modules Installed to select ANN-BUS addresses for the mod-
NO
ule(s). The only difference between the two programming screens are the addresses. The Primary Bus module
addresses will have a prefix of "1-" while the Secondary Bus module addresses will have a prefix of "2-". The
following screen will be displayed for either bus circuit.
Module Type Screen #1
NO
ANN-BUS MODULES
1=ADDR. X-1
NONE
2=ADDR. X-2
NONE
3=ADDR. X-3
NONE
ANN-BUS Modules Screen #1
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE
NONE
ANN-BUS Address Screen
ANN-BUS MODULE TYPE
1=ANN-I/O MODULE
2=ANN-S/PG MODULE
3=ANN-LED MODULE
Module Type Screen #2
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE
ANN-I/O
2=MODULE OPTIONS
ANN-BUS Address Screen
ANN XXX
1=CLASS A
NO
ANN-BUS Screen #2
ANN-BUS MODULE TYPE
1=ANN-RLY MODULE
2=ANN-ACC
2=ANN-ECC
Module Type Screen #3