Control Panel Installation

4.7 6855 Remote Annunciator Installation

The optional model 6855 Remote Annunciator, is shown in Figure 4.13. The 6855 can be surface or flush mounted. Up to 12 annunciators
can be added to the 6808 system in any combination.
6855 installation involves the following steps:
1.
Ensure power is off at the panel.
2.
Mount the 6855 in the desired location (see Section 4.7.1).
3.
Connect the 6855 to the panel (see Section 4.7.2).
4.
Use the DIP switches on the back of the 6855 to assign an ID#. (See Section Section 4.15.1.)
5.
The new 6855 module must be added to the system through programming. JumpStart Auto-Programming will add the module
automatically (see Section 7.1). You can also add it manually (see Section 8.2.2). Select a name, if desired.
4.7.1 Mounting the 6855
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted.
34
FACP
EXT. COMM
Figure 4.12 SBUS Class B Wiring
Figure 4.13 6855 Remote Annunciator
supervised,
power-limited
Model 6855
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
6855 Remote Annunciator Installation
SBUS device