RA-100 Remote Annunciator Installation

SLC IN
_
+
NOTE: The earth ground jumper on the 5495/5499 must be removed in this configuration.
4.7 RA-100 Remote Annunciator Installation
The optional model RA-100 Remote Annunciator, is shown in Figure 4.13. The RA-100 can be surface or flush mounted. Up to eight RA-
100 annunciators can be added to the IFP-75 system in any combination.
RA-100 installation involves the following steps:
1.
Ensure power is off at the panel.
2.
Mount the RA-100 in the desired location (see Section 4.7.1).
3.
Connect the RA-100 to the panel (see Section 4.6.3).
4.
Use the DIP switches on the back of the RA-100 to assign an ID#. (See Section Section 4.13.1.)
5.
The new RA-100 module must be added to the system through programming. JumpStart Auto-Programming will add the module
automatically (see Section 7.1). You can also add it manually (see Section 8.2.2). Select a name, if desired.
4.7.1 Mounting the RA-100
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted.
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
FACP
SLC OUT SLC PROG
SBUS
_
_
_
A
B
+
+
+
Figure 4.12 Powering SBUS Devices from 5495 or 5499
Figure 4.13 RA-100 Remote Annunciator
SBUS Device
– +
NAC 1
NAC 2
Farenhyt™ Series
Model RA-100
5495 or 5499
A
B
1
2
3
4
AUX
OUT4
H5-
H5+
H4-
H4+
supervised,
power-limited,
Control Panel Installation
5
6
7
8
OUT3
OUT2
H3-
H3+
H2-
H2+
Class B
35