Ra-100 Remote Annunciator Installation; 1: Mounting The Ra-100 - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Control Panel Installation

4.5 RA-100 Remote Annunciator Installation

Figure 4.11 The optional Model RA-100 Remote Annunciator, is shown in Figure 4.12. The RA-100 can be surface or flush mounted. Up
RA-100 installation involves the following steps:
1.
Make sure power is off at the panel.
2.
Mount the RA-100 in the desired location (see Section 4.5.1).
3.
Connect the RA-100 to the panel (see Section 4.5.1).
4.
Use the DIP switches on the back of the RA-100 to assign an ID# to the RA-100 (see Section Section 4.11.1).
5.
The new RA-100 module must be added to the system through programming. JumpStart Auto-Programming will add the module
automatically (see Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired.
4.5.1 Mounting the RA-100
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted.
Flush Mounting
This section of the manual describes flush mounting.
Follow these steps to flush mount the RA-100
1.
The back box dimensions are 9-9/32" w x 8-3/8" h. The minimum depth 2". The back box can be mounted prior to the complete
installation of the RA-100 using any of the mounting holes shown in Figure 4.13.
2.
Remove the knockout holes as needed for wires. See Figure 4.14 for backbox knockout locations.
32
to 8 RA-100s can be added to the IFP-75System in any combination. .
Figure 4.12 Model RA-100 Remote Annunciator, Front View
Mounting Holes
Mounting Holes
Figure 4.13 Back Box Mounting Holes
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
RA-100 Remote Annunciator Installation