Installing Cables Outside The Pre-Fab. Module; Connecting Input Power Cables For The Pre-Fab. Module - Huawei FusionDC1000A Installation Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario)
9
Installing Cables Outside the Pre-fab.
9.1 Connecting Input Power Cables for the Pre-fab.
Module
Preparations
Tools: crimping tool, Phillips screwdriver, adjustable wrench, cable cutter, heat gun
Materials: cable tie, cable, terminal, heat shrink tubing
Skill requirement: skilled technician
Procedure
Step 1 Open the door of the power PDB.
Step 2 Remove the plugs from the two cable holes at the bottom of the power PDB.
Figure 9-1 Removing the plugs from the cable holes
Step 3 Remove the transparent cable protection panel from the power PDB busbar.
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.

9 Installing Cables Outside the Pre-fab. Module

Module
97