Figure 8-31 ASD battery wiring diagram
----End
8.4.4 Removing the Fire Cylinder in the SmartLi Cabinet and
Filling Extinguishant
Preparations
The fire cylinder of the fire detection and extinguishing equipment needs to be
filled with extinguishant onsite.
Tools: insulated socket wrench, insulation gloves, Phillips screwdriver, key to the
cabinet door, torque wrench, pipe cutter, and pipe holder
Procedure
Step 1 Check that the fire cylinder valve is closed (vertical to the cylinder).
Figure 8-32 Checking the fire cylinder valve
Step 2 Open the rear door of the cabinet and remove the fire cylinder.
1.
2.
Issue 01 (2021-04-20)
Remove the fire cylinder fastener.
Take out the fire cylinder.
Copyright © Huawei Technologies Co., Ltd.