Refrigerant Frostbite
Refrigerant leakage may cause frostbite. Take protective measures (for example,
wear antifreeze gloves) when handling refrigerant.
Storage and Recycling

1.7 Pre-fab. Module Safety

Issue 01 (2021-04-20)
Do not store devices near a heat source or under direct sunshine.
Keep devices away from fire or high-temperature objects, especially devices
injected with pressurized nitrogen or refrigerant; otherwise, explosion or
refrigerant leakage may occur, causing personal injury.
The sign indicates that the product cannot be disposed of with other
wastes that have a shell in European Union (EU) areas. To avoid environment
pollution and harm to human health, wastes must be classified and recycled.
This also promotes resource reuse. When recycling a device, fill in the device
information in the recycling collection system or contact your dealer for help.
The dealer can help you recycle devices in a safe and environment-friendly
way.
Ensure that the installation environment meets the following requirements:
The ground must be solid without spongy or soft soil, and is not prone to
subsidence.
The site must be clean and far away from dust, oil fume, and harmful
gas.
The site must be far away from corrosive, flammable, and explosive
materials.
The site must be far away from sources of strong variation, loud noises,
and strong electromagnetic interference.
The site must not be located in a low-lying land or an area prone to
water accumulation. It must be above the highest water level of the local
area.
Do not install other equipment on the top of a pre-fab. module without
evaluation by Huawei.
When performing operations (such as installing an awning or outdoor unit)
over the top of a pre-fab. module, take measures to protect the top of the
pre-fab. module against damage. Do not perform operations such as arc
welding, drilling, and cutting on the top of a pre-fab. module.
Do not smoke or use open flame inside a pre-fab. module.
Before performing fire operations inside a pre-fab. module, obtain the
customer's approval and the required work permit and fully evaluate risks.