Wiring to Inductive Loads
When wiring outputs to inductive loads, use of external suppression circuits is
recommended. If possible, the external suppression circuits should be
connected across the actual load. If that is not possible, external suppression
circuits should be connected to each point that will drive an inductive load.
AC Inductive Loads
For AC inductive loads, the snubber network
should consist of a 250 V AC, 0.1µF capacitor
connected in series with a 100 Ohm ½ Watt or
higher resistor. A capacitor with a different
working voltage may be chosen, as appropriate
for the application.
Recommended snubber packages include
104M06QC100 or 104M06RL100 from Paktron.
Isolated Outputs, AC
Isolated Output
Return for Isolated
Output Point
Grouped Outputs, AC
Output Point
A18 and/or
B18
2-20
VersaMax Modules, Power Supplies and CarriersUser Manual
Point
100 Ohm
½ Watt
Inductive
Load
0.1µF
250VAC
100 Ohm
½ Watt
Inductive
Load
0.1µF
250VAC
DC Inductive Loads
For DC inductive loads, a diode should be placed
across the load as shown below. Recommended
diodes include:
1N4934 100 V, 1A;
1N4936 400 V, 1A;
1N4937 600 V, 1A.
These diodes are available from most
manufacturers.
Isolated Outputs, DC
Isolated Output
Point
Diode
Return for Isolated
Output Point
Grouped Outputs, DC
Output Point
Diode
A18 and/or
B18
Inductive
Load
Inductive
Load
GFK-1504N