Jumper Selection
If no jumper is installed outputs hold their last state (the last commanded value
from the backplane) if backplane power or communications are interrupted or
the PLC is stopped. With a jumper installed, if such conditions occur outputs
default to 4mA. This should only be changed with field power and backplane
power removed.
Wiring Example
GFK-1504N
Chapter 11 Analog Output Modules
Analog Output Module, 12 Bit Current, 4 Channels
Jumper
None
JMP 1
Load
Load
Jumper installed =default to 4mA
no jumper = hold last state
-
24VDC
+
Default
Hold Last State
4mA
IOUT 1
RET 1
Shield
IOUT 4
RET 4
Shield
JMP 1A
JMP 1B
Field Return
Field Power