Discrete input/output module IC200MDD850 provides 4 isolated discrete inputs
and 8 relay outputs. Inputs are positive logic or sourcing-type inputs; they receive
current from AC input devices and return the current on the common. Each input
has its own return. Outputs are individually-isolated relays which can drive a
maximum of 2 A per output. These are Form A relay outputs where the contact is
closed when the host CPU is active and the corresponding output logic bit is "1".
Power for module operation comes from the backplane. Output loads must be
powered by an external source.
Intelligent processing for the module is performed by the CPU or NIU. The module
provides 4 bits of discrete input data and receives 8 bits of discrete output data.
LED Indicators
Individual green LEDs indicate the On/Off states of the output points and input
points. Operation of the output LEDs is logic driven and independent of the load
conditions.
The green OK LEDs are ON when backplane power is present to the module.
GFK-1504N
Chapter 9 Discrete Mixed Modules
Mixed Module, Output Relay 2.0 A per Pt Isolated 8 Points /
Q
1
2
3
4
5
6
7
8
1
2
3
4
I
IC200MDD850
Input 240 V AC Isolated 4 Points
OK
IC200MDD850
OUT RLY 2A
ISO 8PT
IN 240VAC
ISO 4PT
1234567
831
OK