Thermal Considerations

The thermal performance specified for modules in this manual requires a
clearance of 5.1 cm (2 in) above and below the modules and 2.54 cm (1 in) on
each side of the modules as shown below, regardless of the orientation of the
DIN rail.
When using a vertical DIN rail, the CPU or NIU module must be installed at the
bottom.
Individual modules have may additional clearance requirements. Refer to
Appendix A.
2.54cm
(1.0in)
2-4
VersaMax Modules, Power Supplies and CarriersUser Manual
5.1cm
(2.0in)
2.54cm
(1.0in)
5.1cm
(2.0in)
5.1cm
(2.0in)
CPU or NIU
at Bottom
2.54cm
(1.0in)
5.1cm
(2.0in)
2.54cm
(1.0in)
GFK-1504N